RSA-TTD1A Room Digital Temperature Transmitter/Controller - ref pag 5

RSA-TTD1A Room Digital Temperature Transmitter/Controller

Applications & Features

  • RSA-TTD1A series are designed for indoor environment temperature measurement and control
  • High performance digital temperature sensor and digital technology applied, ensure accurate measurement, fast response & good long term stability
  • Multiple outputs, over voltage and reverse polarity protection, high reliability and anti-interference capability
  • Optional relay for alarm or ON/OFF control
  • Light and state of art housing, easy installation
  • Wide working temperature range and fast response
  • All electrical terminals are on the inside bottom, avoid any possible destroy to PCB when wiring
  • LCD & function keys can set parameters and calibrate
    output, thus the product becomes a stand alone controller

Specifications

Sensor: Digital temperature sensor
Range: See models
Output: 4'20mA (3 wires) &0'10VDC, RS485/ModbusNote 1
Output Load: ≤500Ω (current), ≥ 2KΩ (voltage)
Relay: 1×SPST, 3A/30VDC, 3A/250VAC
Accuracy: ≤±0.5°C@0'85°C,see accuracy curve
Power: 16'28VAC/16'35VDC
Display & Keys: Optional LCD display and function keys, see details on LCD & Keys operation
Display Resolution: 0.1°C
Work Temp.: 0'70°C, 0'95%RH (Non cond.)
Storage Temperature: -30'70°C
Housing: ABS+PC
Protection: IP30
Approval: CE
Optional Accuracy: 0.25°C @ -20 ~105°C (Add “H” after part number)
Accuracy curve:

Models



Note 1: the communication protocol is Modbus RTU
Note 2: Refer to working environment ambient guide GB/T4200 and WBGT etc, the relay default settings are ON-30.0°C/OFF-29.5°C,and also can be set through LCD & function keys.

TCL Low Temperature Controller

Applications & Features

  • RSA-CTB has a long sensing capillary filled with vapor. When any part of the component is below the temperature set point, the contact will actuate
  • It is applicable to cold water coil or other surface temperature alarm for liquid pipe or air in duct
  • Contact actuate quickly at the set point
  • Readable scale, easy to operate the set point

Specifications

Models and parameters: See below tables
Working environment:-10'70°C, <95%RH, non cond. Sensitive element operating temperature range:-30'80°C Electrical connection: screw terminal, 1.5mm2 wire, PG9 Electric strength: AC1500V/1min (AC1800V/1s) Insulation: ≥100MΩ in normal status, ≥10MΩ in moisture status Sensitive element: copper capillary, φ2mm, 1.5/3/6m long House: cover PC, body fireproof ABS
Protection: IP54
Contact life: ≥ 105
Weight: RSA-CTB -1A:220g; TCL-3A:250g; TCL-6A:310g
Approval: CE

Models


Download Catálogo